PSU-24VDC/ASi-4A.
datasheel.
Product characteristics |
||||||||||
Power supply |
||||||||||
DC convertor 24 V DC for AS-i system voltage |
||||||||||
Integrated data decoupling |
||||||||||
Application |
||||||||||
Application |
AS-i system voltage for masters, sensors, actuators and modules |
|||||||||
Electrical data |
||||||||||
Input voltage range [V] |
24 DC; – 25 % / + 35 % |
|||||||||
Nominal voltage [V] |
24 DC |
|||||||||
Output voltage (AS-i) [V] |
30.5 DC |
|||||||||
Output power [W] |
122 |
|||||||||
Output power peak [W] |
134; briefly to load bus capacities after power on |
|||||||||
Power reserve [%] |
10 |
|||||||||
Output current (AS-i) [A] |
4 |
|||||||||
Residual ripple [mVpp] |
< 50 |
|||||||||
Switch-on peak current [A] |
2 (24 V DC) |
|||||||||
Inrush current limitation |
yes |
|||||||||
Efficiency [%] |
90.5 (24 V DC) |
|||||||||
Short-circuit proof |
yes |
|||||||||
Overload protection |
yes |
|||||||||
Overload performance |
constant output current |
|||||||||
Overvoltage protection [V] |
< 36 |
|||||||||
Excess temperature protection |
yes |
|||||||||
External input protection |
≤ B-10 A / ≤ C-8 A |
|||||||||
Power-on delay time [ms] |
≤ 650 |
|||||||||
Derating [W/K] |
3 (60…70 °C) |
|||||||||
Mains buffering time [ms] |
6 (24 V DC) |
|||||||||
Protection class |
III |
|||||||||
Input current [A] |
5.5 (24 V DC) |
|||||||||
Power loss [W] |
12.7 (24 V DC) |
|||||||||
Back feeding protection [V] |
≤ 35 DC |
|||||||||
Block diagram |
||||||||||
Output curve |
||||||||||
Characteristic curve for degree of efficiency / power loss |
||||||||||
Characteristic curve for derating |
||||||||||
Characteristic curve for mains buffering time |
||||||||||
Outputs |
||||||||||
Parallel connection of outputs |
no |
|||||||||
Series connection of outputs |
no |
|||||||||
Environment |
||||||||||
Ambient temperature [°C] |
-25…70, observe the free space for convection (see operating instructions) |
|||||||||
Storage temperature [°C] |
-40…85 |
|||||||||
Max. relative air humidity [%] |
95, (IEC 60068-2-30) |
|||||||||
Protection |
IP 20 |
|||||||||
Degree of soiling |
2; (IEC 62103) conductive soiling not permitted |
|||||||||
Tests / approvals |
||||||||||
EMC |
|
|||||||||
UL |
UL 508 (Industrial Control Equipment) |
|||||||||
Shock resistance |
|
|||||||||
Vibration resistance |
|
|||||||||
MTBF [h] |
1247000 |
|||||||||
AS-i classification |
||||||||||
AS-i certificate |
98801 |
|||||||||
Mechanical data |
||||||||||
Housing materials |
steel sheet |
|||||||||
Installation |
rail TH35 (to EN 60715) |
|||||||||
Weight [kg] |
0.597 |
|||||||||
Displays / operating elements |
||||||||||
Function display LED |
green (indication AS-i voltage) |
|||||||||
Electrical connection |
||||||||||
Connection |
screw terminals |
|||||||||
Wiring
|