Active AS-i module
Mounting on DIN rail.
Combicon connector for sensor connection.
4 analogue inputs 4…20 mA.
Supply either from AS-i or an external 24 V source.
For the connection of 2-wire, 3-wire or 4-wire sensors
Electrical data |
|||
Electrical design |
4 inputs 4…20 mA |
||
Operating voltage [V] |
26.5…31.6 DC; "supply class 2" to cULus. |
||
Current consumption from AS-i (without external supply) [mA] |
53 |
||
Current consumption from AS-i (with external supply) [mA] |
28 |
||
Current consumption from external supply 24 V DC [mA] |
10 |
||
Internal resistance |
50 Ω |
||
AS-i interface reverse polarity protection |
yes |
||
Inputs |
|||
analogue |
|||
Analogue input |
4…20 mA |
||
Sensor supply |
AS-i / external (to PELV) |
||
Max. total current load for all inputs (without external supply) [mA] |
100 |
||
Max. total current load for all inputs (with external supply) [mA] |
500 |
||
Short-circuit proof |
no |
||
Max. operating voltage [V] |
24 DC ± 20 % |
||
Resolution [Bit] |
16 (1 bit = 1 µA) |
||
Measuring / setting range |
|||
value range |
4…20000 |
||
Accuracy / deviations |
|||
Accuracy [% of the final value] |
0.5 |
||
Response times |
|||
A/D conversion |
1 channel: 20 ms / 2 channels: 120 ms / 3 channels: 180 ms / 4 channels: 240 ms |
||
Environment |
|||
Ambient temperature [°C] |
0…70 |
||
Storage temperature [°C] |
-20…85 |
||
Protection |
IP 20 |
||
Tests / approvals |
|||
EMC |
EN 50295 |
||
AS-i classification |
|||
AS-i profile |
S-7.3.E |
||
I/O configuration [hex] |
7 |
||
ID code [Hex] |
3.E |
||
AS-i certificate |
in preparation |
||
Mechanical data |
|||
Housing materials |
PA 6.6 |
||
Weight [kg] |
0.159 |
||
Displays / operating elements |
|||
Operation LED |
green (indication AS-i voltage / indication ext. 24 V AUX) |
||
Error LED |
red (FAULT: AS-i communication error / periphery fault) |
||
Function display LED |
yellow (indication channels 1…4 / indication diagnosis DIAG) |
||
|
|||
Accessories |
|||
Accessories (optional) |
|
SmartLine25 4AI (C) C IP20.
|
Comments are closed.